Connection and termination set for parallel heat- ing systems in terminal technology for use in ex- plosive hazard areas

Type HBR-IAL8190 °C

The HBR-IAL8EX system includes a quick and simple to fit connection technology to connect the connecting cable and heating tape and termination based on a screw connection. The dimensions can be selected so the system can be accommodated beneath the thermal insulation. Neither a hot-air gun nor any other special tool is required for configuration.

  • Temperature stability up to +190°C
  • Current load capacity up to 20 A
  • For parallel heating systems HBR-ILLw, ILH, ILS
  • Very stable, as completely made of nickel-plated brass
  • Compact dimensions
  • Alternative: Low temperature version up to 135°C, only for HBR-ILLw heating tape

Self-configuration
190°C HBR-ILH/ILS Type HBR-IAL8Ex-HKSS
135°C HBR-ILL Type HBR-IAL8Ex-MKSS
Temperature class T6 / T5 / T4 / T3
Terminal range for supply line 7.0 - 10.5 mm
Terminal range for heating conduc- tor 4.7 x 10 - 6.5 x 13 mm
Max. current load capacity 20 A AC
Measurement voltage 12...400 V AC
Terminal cross section 2.5 mm²
Protection type IP65
Length connection/termination 110 mm / 70 mm
Diameter 25 mm
Weight connection/termination 168 g / 116 g
Material Nickel-plated brass
Marking (Ex) II 2G Ex e IIC T6/T5/T4/T3 Gb
(Ex) II 2D Ex tb IIIC T195°C Db IP65
Connecting cable Ex (option) by the metre
HBR-ALF-25 3 x 2.5 mm² 200 °C
HBR-ALR-15 3 x 1.5 mm² 135 °C