back to product overview
Self-optimising 2-zone controller for the Switch cabinet installation on Top-hat rail
HT 85 series
Thanks to its free configurability and compact design, theHT85is a universal controller for machine, plant and apparatus engineering. When designing this appliance, particular emphasis was placed on simple and clear handling. The mounting on standard rails and the removable terminals (plug-in blocks) also guarantee use under difficult installation conditions in the switch cabinet.
Power supply | 100-240 Volt AC / 48 Hz...62 Hz; approx. 3 VA 24 Volt DC / +/- 20%; 3 W |
Sensor types | Pt100, Pt1000, Fe-CuNi (J), NiCr-Ni (K), Ni120, sensor breakage protection, sensor polarity reversal check, short-circuit monitoring |
Error limit | Calibration accuracy: <0.25%; linearity error: < 0.2% |
Actual/target display | 7-segment display; 3+ digits |
Measuring range | -20 ... 999 °C (depending on the sensor type) |
Output Triac | 230V AC; 600W/channel; max. total power 1200 W 24V DC; 65w/channel; max. total power 130W |
Output Load relay | Relay NO contact max. 250V AC, max. 16A, resistive load |
Output Logic | Voltage, bistable; 0/12V DC, Ri=680 Ohm |
Output Alarm relay | Changeover contact, 24V DC 1A, no mains voltage permitted |
Inputs | 4-20 mA continuous inputs for external setpoint specification |
Protection class | IP 20 (DIN 40050) |
Controller dimensions | 72 x 70 x 90 mm (H x W x D) without clamps |
Connections | plug-in connection terminals |
Electrical connections | Cross-section terminals 1-12: 0,2 ... 2.5 mm² cross-section terminals 20-38: 0,14 ... 1.5mm² |
Special functions | Self-optimisation of the controller parameters for quick adaptation to the controlled system. Safety operating mode can be set by connecting the relays upstream of the triac control to switch off in the event of a fault alarm, setpoint limitation and setpoint correction. |
Installation housing for HT 55 | |
Housing dimensions HZ-EK 2 | for 1 unit 125 x 200 x 122 mm |
Housing dimensions HZ-EK 4 | for 2 units 200 x 200 x 122 mm |
Housing dimensions HZ-EK 6 | for 3 units 250 x 200 x 122 mm |
HT 55 protection type | IP65 (EN 60529) in installation housing |
Design | in accordance with VDE 0631 |